* Copland Hermetic Commercial Compressor
Horsepower: 2 3/4
Voltage: 200-230/3/60
Rated Load Amps: 11.4
Oil: Mineral
Mount (In.): 7.5 x 7.5
Height (In.): 13 7/8
Shipping Weight (Lbs.): 72
Connection Suction (In.): 3/4
Connection Discharge (In.): 3/8
Connection Type: Sweat
Refrigerant: R22
Capacity (BTUH): 32,000
Engineered Items: Yes
LTL Only: Yes
Oil_short: MIN
Vendor: Copeland Corporation
Replaces Compressor Part Numbers:
CR32K6-TFS
CR32K6-TF5
P021-3251
GB10RV001
CRG3-0250-TF5
P021-3151
34B0045N03
COM04503
COM4503
66542802
GB10RV001
521353
711091
711091
P021-3251
P021-3151
10481809
1054609
1083930
10481809
912967
39311C2
1059517
1147106
1147119
CR32K6TF5
CR32K6-TF5
CR32K6-TF5-970
CR32K6TF5970
CRF10250TF5
CRG30250TF5
CR33KQ-TF5
CR33KQTF5-980WB
CR33KQTF5980WB
CR33KQ-TF5-980WB
CARCR33KQTF5980WB
CARB94682
CR33KQTF5
CARCR33KQTF5980WB..
Used in Anana Goodman Janitrol Air Conditioning Models:
RCA36A3A
P1173305C
RCB36A3A
P1205205C
Used in Bryant Carrier Air Conditioning Models:
38TKB036500
38CKW036520
38CKC036510
561CPX036000ABAA
561GPX036000ABAA
PA10PA03600GAAAA
PA10PA036000AAAA
38CKG036510
561WPX036000ACAA
50RVC036501
50RHC036501
593CPX036000ABAA
Used in Rheem Ruud Air Conditioning Models:
Used in Trane Air Conditioning Models:
Used in Air Conditioning and Heating Brands: Airquest, Arcoair, Clare, Comfortmaker, Heil, Kenmore, Tempstar, Snyder General, Intercity Products, Whirlpool.
Used in ICP Equipment Models:
PAA036N1HA
PAB036N1HA
PAMC36H1
PAMC36HA
PGA036D1HA
PGA036D2HA
PGA036F1HA
PGAC36C1HA
PGAC36C1HC
PGAC36D1HA
PGAC36D1HC
PGAC36E1HA
PGB036D1HA
PGB036D1HC
PGB036D2HC
PGB036F1HA
PGB036F1HC
PGMD36H060A
PGMD36H090A
PGMF36H0901
PGMF36H090A
PGMF36H090C
PGMF36H1351
PGMF36H135A
PGMF36H135C
PGMG36H090C
* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES
Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.
* SINGLE PHASE BURN
Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.
Correction:
(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.
* HALF WINDING SINGLE PHASE BURN
In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.
Correction:
(1) Replace contactors with properly sized contactors.
* HALF WINDING BURN
Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.
Correction:
(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.
* PRIMARY SINGLE PHASE BURN
Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.
Correction:
(1) Check primary side of a delta to wye main power transformer.
* START WINDING BURN
The start winding only of a single-phase motor is uniformly overheated or burned.
Correction:
(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.
* SPOT BURN
A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.
* SHORTED TERMINALS
A break down of the insulation between terminals and compressor body generally the result of over torque terminals.