* Copland Commercial Compressor
•236B8E
•>
* Compressor Performance:
Evap (F)/Cond (F):45/130
RG (F) Liq (F): 65/115
Capacity (Btu/hr): 40500
Power (Watts): 4030
Current Amps: 15.2
EER (Btu/Wh): 10.0
Mass Flow (Lbs/hr): 595
Sound Power (Dba):74.0
Vibration (mils (peak-peak): 2.5 AVE
* Compressor Mechanical:
Number of Cylinders:2
Bore Size (in): 1.96
Stroke (in): 0,821
Overall Length:10.375"
Overall Width: 9.094
Overall Height:14.812
Suction Size (in): 7/8"
Discharge size (in): 1/2"
Initial Oil Charge (oz): 45
Oil Recharge (oz): 43
CIR (in 3/Rev): 4.954
CFH (ft 3/hr):498.8482.
* Compressor Electrical Data:
Voltage: 200/240
Phase: 3
RLA: 16.0
LRA: 97.0
MCC Amps:
RPM:
Max Operating Current:
UL File No:
Replaces Part Numbers:
CR47KQTF5980WB
015-03464-005
01503464005
04DG1124B
S51417
P128833
PCR47KQ-TF5
PCR47KQTF5
1059518
P021-4751
P0214751
CRL3-0350-TF5
CRL0350TF5
A093
CRL0-0350-TF5-523
CRLO-0350-TF5-523
CRLO-0350-TF5
CRL0-0350-TF5
CR47KQ-TF5-980WB
CR47KQ-TF5
H23A423DBLA
B9266-204A
CARB9266204A
CARB93395
CARCR47KQTF5B92
Used in Goodman, Janitrol Air Conditioning Models: CK49-3, CPKE48-3, CPLE048-3, PCK048-3, PHK048-3, PGB048100-3, PGB048150-3.
* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES
Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.
* SINGLE PHASE BURN
Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.
Correction:
(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.
* HALF WINDING SINGLE PHASE BURN
In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.
Correction:
(1) Replace contactors with properly sized contactors.
* HALF WINDING BURN
Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.
Correction:
(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.
* PRIMARY SINGLE PHASE BURN
Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.
Correction:
(1) Check primary side of a delta to wye main power transformer.
* START WINDING BURN
The start winding only of a single-phase motor is uniformly overheated or burned.
Correction:
(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.
* SPOT BURN
A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.
* SHORTED TERMINALS
A break down of the insulation between terminals and compressor body generally the result of over torquing terminals.