Accredited Business Go Daddy Authorize.net
Click Here to Learn More
(866) 432-8551 Toll Free
Mon to Fri 10am to 6:30pm EST
Confused? Get help finding the right part

Rollover image above to zoom

***OBSOLETE - REPLACED WITH COMP108KCTFD*** 9 Ton 460 Volt Copelaweld Hermetic Commercial Compressor

Price: $0.00 
Excl. Shipping
Call For Availability
SKU: COMP20900TFD
(See Product Details Below for Manufacturers Part Numbers)

Suitable for air conditioning, R22 applications charged with mineral oil.


• RL (R suffix) connection requires valves or adapters, not provided

• Mount: 8.7" x 8.7"

• Capacity rated: 45
•F evaporator; 130
•F condensing

* Copland Replacement Compressor

Sweat Connection
Compressor Specification:

Evaporator (F) Cond (F):45/130
RG (F) Liq (F): 65/115
Capacity BtuH:87500 to 114000
Power Watts:8400
Current Amps:16.5
EER BtuH/Wh:<10.4br> Mass Flow Lbs/Hr:1280
Number of Cylinders:4
Bore Size (in):2.188
Stroke (in):0.8
Overall Length:14.25"
Overall Width:13.25
Overall Height: 18.44
Suction Size:1-1/8"
Discharge Size:3/4"
Initial Oil Charge (oz):128
Oil Recharge (oz):124
RLA: 19.3
LRA Amps:96.5
MCC Amps:27.0
Max Operating Current:
UL File No:SA-2337
CSA File No:LR3104C

Replaces Compressor Part Numbers:

P021-11071 P021-9971 P031-9971 302523-302 302523-352 50EC662600 685347-32 912610 015-02025-700 015-02025-000 39H3701 39H37 8000-5509 015-01460-011 014-01460-005 802003276 GB30UK010 802003276 100152 1148990 015-01460-005 015-02025-700 015-02025-000 015-01460-011 015-02025-000 521148 1148990 100156 100152 100266 2003276 P021-9971 302523-352 50EC662600 55-40509-05 55-40509-13P 8000-5560 55-40509-13 D-29656-2 55-40509-13 55-40509-13S 1150049 60440039 1222-746 1222746 55-40509-13S 55-40509-13 COM03185 COM3185 COM02087 COM2087 4D631 D75-25 68524732 CARB93761 912610 100-104 BRG20900TFD BRG20900TFDS BRG-20900-TFD BRG20900-TFD-903 BRG20900TFD903 BRG2-0900-TFD-903 BRG4-0900-TFD CARBRG20900TFD

Used in Equipment Models:

Used in Carrier BDP Air Conditioning Models:

50VQN240FMC6 0014 A 50VQN240FMN6 0014 A 50VQA120FMC6 0014 50VQA120FMN6 0014 50VQA240FMC6 0014 50VQA240FMN6 0014 50CD008900 0015 50CD008910 0015 50VQK120FMC6 0014 A 50VQK120FMN6 0014 A 50VQK240FMC6 0014 A 50VQK240FMN6 0014 A 50CH008900 0015 50CH008910 0015 50VQD120FMC6 0014 50VQD120FMN6 0014 50VQD240FMC6 0014 50VQD240FMN6 0014 50LW024600 0071 558CEX240000AA 0077 569AEX090000AAAA 0019 580CEZ240255AA 0082 580CEZ240500AA 0082 50LJ024600 0071 48LJD024600 48LJE024600

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torquing terminals.

I called trying to find out what happened to the rest of my order and was surprised to hear a warm and kind voice willing to do whatever it takes to find answers and follow through with her promise. Amanda is an asset worth holding on to and a credit to your company. She was very professional, helpful and courteous while assisting me with my order. I would most definitely assign her an A+ in customer service."
Donald "Brad" Thomas

I would like to thank you for your hard work in getting us our part in a timely fashion. You were very helpful and you understood the severity of the situation and did a wonderful job in getting the part to us. Thanks again and please share this with your boss! You were outstanding!"
Todd Mills

Share This:
Have Questions? Prefer to order by phone?
Our parts Experts are happy to help!

Call Monday to Friday 10am - 6:30pm EST
1-866-432-8551 or Email our Parts Experts
Accredited BusinessGo DaddyAuthorize.net
Amanda I want to thank you, the blower fan work perfectly. Thank you so very much."
Bill K Roberts
Amanda, Thank you very much again, I have been looking for this part for about two weeks and getting very frustrated in the process of the search, you were very helpful!!"
Ken Holm
Why Buy From Us?
110% Lowest Price Guarantee
Over 500,000 Parts in Stock
Same Day Shipping on Orders Received Before 3pm EST (Mon-Fri)
Nationwide Distribution Centers for Fast Delivery
Choose from UPS Next-Day, 2-Day, 3-Day and Ground Service
We Supply Retail and Wholesale
Order from us.
Risk Free, with
Our Triple Guarantee
Guarantee 1
No hassle, 30-day returns policy
Guarantee 2
110% Lowest price guarantee
Guarantee 3
90-day warranty
Sign up for Special Offers Directly from AmericanHVACParts.com
AmericanHVACParts.com | 548 N. 13th Ave., Suite 302 | Upland, CA 91786
© 2005-2014 AmericanHVACParts.com. All Rights Reserved.