T-5002 Room Temperature Transmitter
The T-5002 Room Temperature
Transmitter measures space or
mass temperature and transmits a
proportional 3 to 15 PSIG (21 to
105 kPa) output signal to an
indicator, receiver-controller, or
Building Automation System for
automatic temperature control.
The space transmitters measure
the temperature of the ambient air;
the mass transmitters measure the
surface temperature of the walls
surrounding the space and
transmit the signal to an optimal
start controller.
Mounting
The T-5002 room transmitter is
installed similarly to the standard
T-4000 series thermostats.
Calibration
The T-5002 has a fixed span and is
factory calibrated. The only
adjustment necessary is shifting the span for special applications or
fine tuning the instrument.
1. Furnish a 20 PSIG (140 kPa)
supply pressure to the
instrument.
2. Attach a transmission gage
(that matches the instrument
range) and test probe to the
output pressure test
connection.
3. Accurately measure the
temperature at the element.
4. Find the
proper transmission pressure
corresponding to the
measured temperature. Be
sure to use the vertical scale
on the graph which matches
the range of the transmitter.
5. Turn the zero adjustment
screw until the output pressure
corresponds to the
temperature at the element.
Replaces Part Numbers: T-5002-201, CART-5002-201